Chiller
Technical Parameter
Model/Item |
AW-20(D) |
|
nominal cooling capacity |
kcal/h |
55384 |
kw |
64.4 |
|
input power |
kw |
21.89 |
power supply |
3PH~380V60HZ |
|
refrigerant |
type |
R22 |
type of control |
thermostatic expansion valve |
|
compressor |
type |
hermetic scroll |
power(kw) |
7.15*2 |
|
condenser |
type |
shell and tube |
cooling water flow(m3/h) |
15.8 |
|
inlet and outlet pipe diameter(inch) |
2-1/2 |
|
evaporator |
type |
tank with coil |
chilled fluid flow(m3/h) |
11.76 |
|
inlet and outlet pipe diameter(inch) |
2-1/2 |
|
pump |
power(kw) |
3 |
lift(m) |
25 |
|
safety protection |
compressor over temperature, over current, high and low pressure, phase sequence, phase-missing |
|
weight |
kg |
900 |
dimension |
mm |
1700*810*1620 |
Note:
1.Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 12℃
Outlet chilled fluid temperature: 7℃
Inlet cooling water temperature: 25℃
Outlet cooling water temperature: 30℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
The temperature range of cooling water is from 18℃ to 35℃;
Temperature difference between inlet and outlet coooling water is from 3.5℃ to 10℃.
We reserve the right to modify the above dimensions or parameters without further notice.